Detalles
Bateria DYNASTY UPS12-490MR 12V 141aH
FEATURES & BENEFITS
- -10 year design life @ 25 ̊C
- -Absorbent Glass Mat (AGM) technologyfor efficient gas recombination of up to 99% and freedom from electrolyte maintenance.
- -3 Year Warranty (refer Dynasty warrantycard, 41-9027)•Patented Long Life Alloy having the lowest calcium levels in the industry - minimizing grid growth, reducing gassing,and extending battery life.
- -Patented UL Recognized Flame-arresting vents in each cell for safety andlong life.
- -Designed with the same recombination,thermal runaway prevention, gassing andflame retardant characteristics of theBellcore 4228 compliant Dynasty Telecomproducts.•Flame retardant polypropylene case andcover compliant with UL94-V2
- -Proprietary Fixed Orifice Plate Pastingtechnology applying active materials on both sides of the grid for consistent cell-to-cell performance, higher capacity and uniform grid protection.
- -Thermally welded case-to-cover bond toeliminate leakage.
- -Can be operated in any orientation.Upright, side or end mounting recommended.
- -Not restricted for air transport - Complieswith IATA/ICAO Special Provisions A67.
- -Not restricted for surface transport -Classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.
- -Not restricted for water transport -Classified as non-hazardous material perIMDG Amendment 27.
SPECIFICATIONS
- -Operating Temperature Range with temperature compensation - Discharge: -40 ̊F (-40 ̊C) to +160 ̊F (71 ̊C)Charge: -10 ̊F (-23 ̊C) to +140 ̊F (60 ̊C)
- -Nominal Operating Temperature Range - +74 ̊F (23 ̊C) to +80 ̊F (27 ̊C)
- -Recommended Maximum Charging Current Limit - C/5 amperes @ 20hr rate
- -Float Charging Voltage - 13.65 ± 0.15 VDC average per 12V unit (6.75 to 6.90 per 6V unit)
- -Maximum AC Ripple (Charger) - 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
- -Self Discharge - Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will requirerecharge sooner than batteries stored at lower temperatures. See C&D brochure41-7272, Self-Discharge and Inventory Control for details.
- -Equalize charge and cycle service voltage - 14.40 to 14.80 VDC average per 12V unit @ 77 ̊F (25 ̊C) (7.20 to 7.40 VDC per 6V unit.)
- -Terminal: Flag - 0.22 in. clearance hole to accept 0.1875 in. or 10-32 bolt (UPS12-100MR)
- -Terminal: Inserted - Threaded copper alloy insert terminal to accept10-32 UNF bolt (UPS12-150MR, UPS12-210MR) 1⁄4-20 UNC bolt(UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MRLP, UPS12-490MR, UPS12-540MR, UPS6-620MR)
- -Terminal Hardware Annual Retorque - 32 in.-lbs (3.48 N-m) (UPS12-100MR)
- -Terminal Hardware Initial Torque: Inserted Terminal - 40 in.-lbs.(4.5 N-m) (UPS12-100MR)Inserted Terminal30 in.-lbs. (3.4 N-m) (UPS12-150MR, UPS12-210MR) 110 in.-lbs. (12.4 N-m) (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MRLP, UPS12-490MR,UPS12-540MR, UPS6-620MR)
Informacion Adicional
Tipo De Producto: | Bateria |
---|---|
Marca: | DYNASTY |
Modelo: | UPS12-490MR |
Folleto: | Descargalo aqui |